MT050B-81315
999999 Items

Data sheet

PDF
/pdfs/MT050B-81315.pdf
docs Y
y
specs Y
y
Includes
3/8 in polyethylene tubing - 90º elbow fitting - Instruction sheet - Male connector fitting - Needle valve - Power cord - Power cord connector lock - PTFE tape - Screws
Product Width
42.86 cm - 16.88 in
Net Weight
16.04 kg - 35.36 lb
gross weight, packed
17.73 kg - 39.08 lb
Product Depth, Packed
53.98 cm - 21.25 in
Product Height, Packed
31.12 cm - 12.25 in
Product Width, Packed
50.17 cm - 19.75 in
Classification
Designed, manufactured and/or distributed under this quality management system,Below Maximum Concentration Value (MCV),Compliant
Product Height
17.15 cm - 6.75 in
Product Depth
41.91 cm - 16.50 in
Operating Temprature
-10 °C to +40 °C (+14 °F to +100 °F)
Dehydrator Type
Automatic Membrane
Volume Capacity, maximum
1699.00 L - 60.00 ft³
Power Cord
Europe power cord with stripped leads
Mount Type
Floor - Rack - Shelf - Wall
Port Count
1
Port Type
3/8 in PE tube
Volume Capacity, minimum
0.00 ft³
Voltage
115 Vac ±10%
Power Consumption
184.0 W
Power Frequency
60/50 Hz
Power Phase
Single
Suggested Curcuit Breaker Size
20 A
Voltage Type
ac
Dew Point
Better than -45 °C (-50 °F) at 95% RH at +40 °C (+104 °F)
Flow Rate
3.40 SLPM - 0.12 SCFM
Regulated Output Pressure Type
factory set
Regulated Output Pressure, maximum
5.0 psig
Alarm Type
Discrete
Excess-Run Alarm
10 minutes, factory set
Low-Pressure Alarm
68 mbar - 7 kPa - 1 psig
Alarm Contact Rating
Form C dry contacts, 2 amps at 30 Vdc
Circuit Breaker Requirement
Electrical connections require separate circuits for dehydrator installation
High-Humidity Alarm
7.5% RH, factory set
Power-Fail Alarm
Loss of input power
Rack Type
EIA 19 in
Rack Units
4
Agency
ISO 9001
Comments (0)
No customer reviews for the moment.